Issue 5 Page 1 of 8
INTELLIGENT
FIRE ALARM CONTROL PANELS
Description
The MR-2900 re alarm system control unit is the heart of a
sophisticated microprocessor-based re alarm system. With
the capability of networking, the MR-2900 is ideally suited
for the varied needs of residential, commercial, industrial,
and institutional applications. The MR-2900 provides both
conventional and addressable input circuits. It has the ability
to ‘software’ congure conventional input circuits for alarm or
supervisory function, and operation with contact devices only,
smoke detectors only, or both smoke detectors and contact
devices with the system having the ability to differentiate
between smoke detector and contact device activation.
Addressable input circuits using addressable analog detectors,
monitoring modules, and control modules are available using
addressable input circuit modules.
The MR-2900 has capacity for up to 24 input circuits, four
general purpose Form C relays, and eight polarity reversing
notication appliance (bell) circuits. System operated relays are
available for alarm, trouble, and supervisory indication.
Input circuit modules are available for conventional circuits and
addressable circuits. The MR-2908 and MR-2928 conventional
input circuit modules each have eight Class B circuits which
can be wired for Class A by utilizing two circuits. The MR-2938
conventional input circuit module supports four Style D (Class
A) smoke detector circuits. The MR-2929 addressable input
circuit module supports eight Style 4 (Class B) circuits or four
Style 6 (Class A) circuits.
The rst eight circuits of the MR-2900 control unit are reserved for
conventional circuits while the remaining 16 circuits can be used
for addressable or conventional input circuits in groups of eight.
Features
Listed to UL 864, 9th edition•
Sophisticated capabilities yet simple to operate•
Conventional and addressable detection circuits•
Adjustable sensitivity•
Day/night sensitivity•
One-person system test capability•
Totally software driven•
Field programmable via PC•
Passcode protection•
History log ≈ 1400 events•
System alarm, supervisory, and trouble relays•
Alarm, supervisory, and trouble LEDs for each zone•
Custom labels per zone•
Remote alarm and trouble annunciation•
Remote detector test capability•
LCD supertwist 80 character (4 x 20) backlit display•
Sprinkler supervision•
Ground fault indication by supervised circuit•
Software denable conventional input circuits•
Conventional input circuits Style B (Class B) or Style D •
(Class A)
Addressable input circuits Style 4 (Class B) or Style 6 (Class A)•
Input circuits programmable for N.O. or N.C. contacts•
Style Y (Class B) or Style Z (Class A) notication appliance •
(bell) circuits
Power limited circuits•
DCLR network communication option•
Optional integrated strip printer•
‘Hot Key’ system controls•
Display of real time•
Signal silence inhibit•
Signal time limit cut-out•
Boolean Logic•
Supports Acclimate and Pinnacle Smoke Detectors•
MR-2920 provides an optional panel mounted printer•
MR-2900/MR-2920
Intelligent Addressable Fire Alarm
Control Panels
SECUTRON INC.
Canada 25 Interchange Way, Vaughan (Toronto), Ontario L4K 5W3 Telephone: (905) 695-3545 Fax: (905) 660-4113 • Web Page: www.secutron.com
U.S.A.
4575 Witmer Industrial Estates, Niagara Falls, NY 14305 Telephone: (888) 695-3545 Fax: (888) 660-4113 • E-mail: [email protected] Catalog Number 1006 • Not to be used for installation purposes.
With the addition of MR-2910 Series network boards, MR- 2900
control units can be networked together to provide additional
input circuits, visual zones, programmable notication appliance
(bell) circuits, and relays. Up to 254 control and annunciator
units can be networked together. The network is a DCLR (Data
Communications Link, Redundant) conguration loop.
Each annunciator can contain up to 576 LEDs (192 zones) for
annunciation purposes, an LCD display for messages, and 16
predened switch inputs for control functions.
MR-2900 Fire Alarm Control Panel
S6619 352-03-E
7165-1656:100
S6619